Clippers RT 10KL
- Topology: On-line Single Phase
- Capacity: 10000VA/10000W
- Power Factor (PF): 1
- Wave Form: Sine wave
- Battery: no internal battery, only for external battery pack
- Intelligent Slot: SNMP, AS400, RS485-Modbus
- Port for External Battery Pack: Yes
- Network Ports: USB, RS-232, EPO
- Parallel Port: Yes
- Box contents: UPS, user manual, software CD, C14-C13 cable, USB cable, tower stands, mounting ears & screws
External Battery Pack Options
Clippers Series
Description

FSP Clippers RT Series is a premium featured online double conversion UPS with Rack/Tower design and high efficiency to reduce customer‘s total cost of ownership. The internal hot-swappable battery increases system reliability and reduce MTTR; the parallel function is designed for future equipment expansion. Its special firmware design can adapt variouse applications like laser printer, ultrasound device and supporting long back-up time with battery monitoring.

- True double conversion
- Output power factor=1
- Output voltage regulation < 1%
- Higher output crest ratio 3:1
- 50Hz/60Hz frequency converter mode
- Emergency power off function (EPO)
- Available for parallel and share current
- 16-20pcs adjustable battery number
- ECO mode for energy saving – 98.5% efficiency
- Support for laser printers and ultrasound systems
- Full time over voltage cut-off and surge protection
- High power factor charger with low ripple current
- Low input THDi to reduce power system pollution
- Adjustable charging current via LCD panel
- Smart battery charger design to optimize battery performance
- Genset compatible
Clippers 6kL | Clippers 10kL | |
Part Number | PPF60A0301 | PPF10L1201 |
Runtime
Run-Time Table per Loading
Minutes (Clippers 10KL + BB-240/09RT)
Minutes (Clippers 10KL + 2*BB-240/09RT)
Specifications
UPS Specifications:
MODEL | Clippers RT 6KL | Clippers RT 10KL | ||
CAPACITY* | 6000 VA / 6000 W | 10000 VA / 10000 W | ||
INPUT | ||||
Voltage Range |
Line Loss |
110~300Vac @ (0~60%) Load
140~300V @ (60~80%) Load 176~300Vac @(80~100%)Load |
||
Low Line Comeback | Low Line Loss Voltage + 10V | |||
High Line Comeback | High Line Loss Voltage – 10V | |||
Frequency Range | 46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system | |||
Phase | Single phase with ground | |||
Power Factor | ≧ 0.99 at 100% Load | |||
OUTPUT | ||||
Output voltage | 208/220/230/240VAC | |||
AC Voltage Regulation | ± 1% | |||
Frequency Range (Synchronized Range) | 46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system | |||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | |||
Overload |
AC mode | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec | ||
Battery mode | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec | |||
Current Crest Ratio | 3:1 max | |||
Harmonic Distortion | ≦ 1 % @ 100% Linear Load; ≦ 4 % @ 100% Non-linear Load | |||
Transfer Time |
Line Battery | 0 ms | ||
Inverter Bypass | 0 ms | |||
Inverter ECO | <10 ms | |||
EFFICIENCY | ||||
AC mode | > 94% | |||
Battery Mode | > 93% | |||
BATTERY | ||||
Numbers | 16~20 | 16~20 | ||
Charging Current | 4 A ± 10% (max.) | 4 A ± 10% (max.) | ||
Charging Voltage | (Battery number*13.65 V) ± 1% | |||
PHYSICAL | ||||
Dimension, DXWXH(mm) |
UPS Unit: 600 x 438 x 88 [2U] |
UPS Unit: 600 x 438 x 88 [2U] |
||
Net Weight (kgs) | UPS Unit: 17 | UPS Unit: 20 | ||
ENVIRONMENT | ||||
Operation Temperature | 0 ~ 40°C (the battery life will down when > 25°C) | |||
Operation Humidity | <95 % and non-condensing | |||
Operation Altitude** | <1000m | |||
Acoustic Noise Level | Less than 55dB @ 1 Meter | Less than 58dB @ 1 Meter | ||
MANAGEMENT | ||||
Smart RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC | |||
Optional SNMP | Power management from SNMP manager and web browser |
Accessories
Battery Pack
Network Management
Support
FSP UPS selector
If you feel hard to identify the differences between our UPSs, try our UPS selector! Input the power capacity and the preferred features to get what you need!

Project Inquiry
Do you still have any concern about the UPS you selected? Or are you facing unique requests in complex site environment? You can consult with us!

Knowledge Center
Not sure about any UPS function, battery, operation or maintenance? Check out our knowledge center. We’ve categorized the knowledge not only by entry or advanced, but also by functions and features!